3412C Generator Set
Maximum Rating
800 ekW
800 ekW
Minimum Rating
635 ekW
635 ekW
Emissions/Fuel Strategy
Low Fuel Consumption
Low Fuel Consumption
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Media
Photos
360° View
Exterior
360° Exterior view. Double click on the image to zoom in on any area of the product.
Details
Specifications
Generator Set Specifications
Spec | Value |
---|---|
Maximum Rating | 800 ekW 800 ekW |
Minimum Rating | 635 ekW 635 ekW |
Emissions/Fuel Strategy | Low Fuel Consumption Low Fuel Consumption |
Voltage | 220 to 480 Volts 220 to 480 Volts |
Frequency | 60 Hz 60 Hz |
Speed | 1800 rpm 1800 rpm |
Duty Cycle | Standby, Prime Standby, Prime |
Engine Specifications
Spec | Value |
---|---|
Engine Model | 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel |
Bore | 5.4 in 137.2 mm |
Stroke | 6 in 152.4 mm |
Displacement | 1648.86 in³ 27.02 l |
Compression Ratio | 13:00:01 13:00:01 |
Aspiration | TA TA |
Fuel System | Pump and Lines Pump and Lines |
Governor Type | ADEM™ A5 ADEM™ A5 |
Generator Set Dimensions
Spec | Value |
---|---|
Length – Maximum | 162.4 in 4125 mm |
Width – Maximum | 78.3 in 1989 mm |
Height – Maximum | 75 in 1906 mm |
Dry Weight – Genset (minimum) | 5761 lb 12700 kg |
Dry Weight – Genset (maximum) | 13275 lb 6021 kg |
Standard Equipment
Air Inlet System
- Air cleaner, single element canister type
- Single element canister type
Control Panel
- High coolant temperature
- Customer data link (Modbus RTU)
- Low coolant temperature
- Low coolant level
- Communications:
- Run/auto/ stop/control
- Engine cycle crank
- Generator temperature monitoring module
- Power factor (per phase & average)
- Remote CAN annunciator
- Serial annunciator module data link
- DC volts
- Frequency (Hz)
- Operating hours.
- Emergency stop pushbutton
- Digital I/O module
- Local annunciator
- Low oil pressure
- Oil pressure (psi, kPa or bar)
- Emergency stop
- Warning shutdowns:
- Volts (L-L & L-N)
- Remote Serial annunciator
- Speed adjust
- Amps (per phase & average)
- Voltage adjust
- EMCP 4.2B
- Overspeed
- coolant temperature
- Digital Indicator for:
- RPM
- Accessory module data link
- Failure to start (overcrank)
- Controls:
- Compatible with the following optional modules:
Cooling System
- Caterpillar extended life coolant
- Radiator with guard (sized for 50 degrees C)
- Fan and belt guards
- Coolant drain line with valve
Exhaust System
- Stainless steel exhaust flex with ANSI style outlet flange
Fuel System
- Primary and Secondary fuel filters
- Fuel priming pump
- Water separator
Generator and Attachments
- 3 Phase sensing
- SR4B self excited
- Class F temperature rise
- VR6B voltage regulator
- Busbar termination
- 12 Leads
- Class H insulation
- 2:1 Volts/Hz
- Reactive droop
Governing System
- Cat electronic governor
Lube System
- Oil drain line with valve
- Lubricating oil
- Oil filter
Mounting System
- Base, formed steel with linear vibration isolators between base and engine-generator
Starting / Charging System
- Battery with rack, cables
- 45 Amp Charging alternator
- Fuel shutoff solenoid
- 24 Volt starting motor
General
- Paint – Caterpillar yellow except rails and radiators gloss black
Optional Equipment
Air Inlet System
- Air cleaner – Dual element
- Air cleaner – Heavy element
- Air cleaner – single element
Certificates
- EU Certification
Circuit breakers
- 4 Pole Circuit breakerswith shunt trip
- 3 Pole Circuit breakers with shunt trip
- Power terminal strip
Control Panel
- EMCP 4.3, EMCP 4.4
- Temperature monitoring package
- Vandal proof panel door
- Generator running VFC
- Earth leakage Ground fault relay
- Common alarm/shutdown relay
Cooling System
- Jacket water heater
- Radiator duct flange
- Radiator removal
Exhaust System
- Muffler 10 dBA attenuation
- Manifold and turbocharger guards
- Muffler 35 dBA attenuation
- Elbow mounting kit
- Through wall installation kit
Fuel System
- Manual fuel transfer pump
- Automatic fuel transfer system
Generator and Attachments
- Internal excitation (IE)
- Anti-condensation heater
- Permanent magnet excitation (PMG)
- Oversize and premium generators
Governing System
- Electronic load share
Lube System
- Manual sump pump
Mounting System
- Fuel tank base (1200 Ltr)
Special Tests / Reports
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- Factory witness test
Starting / Charging system
- Oversize battery set
- Battery chargers
- Heavy duty starting system
- Battery disconnect switch
- Battery removal
Enclosures
- DC lighting package
- Weather protective enclosure (WP)
- Sound attenuated enclosure (SA)