Cat Generator Set Package
Main content
Cat
3412C | 800 kVA 50Hz Generator Set
Maximum Rating
680 kVA
680 kVA
Minimum Rating
680 kVA
680 kVA
Emissions/Fuel Strategy
Low Fuel Consumption
Low Fuel Consumption
Overview
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Media
Photos
360° View
Exterior
360° Exterior view. Double click on the image to zoom in on any area of the product.
Details
Specifications
Generator Set Specifications
Spec | Value |
---|---|
Maximum Rating | 680 kVA 680 kVA |
Minimum Rating | 680 kVA 680 kVA |
Emissions/Fuel Strategy | Low Fuel Consumption Low Fuel Consumption |
Voltage | 380 to 415 Volts 380 to 415 Volts |
Frequency | 50 Hz 50 Hz |
Speed | 1500 rpm 1500 rpm |
Duty Cycle | Standby, Prime Standby, Prime |
Engine Specifications
Spec | Value |
---|---|
Engine Model | 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel |
Bore | 5.4 in 137.2 mm |
Stroke | 6 in 152.4 mm |
Displacement | 1648.86 in³ 27.02 l |
Compression Ratio | 13:01 13:01 |
Aspiration | Turbocharged, Air to Air Aftercooled Turbocharged, Air to Air Aftercooled |
Fuel System | Pump and Lines Pump and Lines |
Governor Type | ADEM™ A5 ADEM™ A5 |
Generator Set Dimensions
Spec | Value |
---|---|
Length – Maximum | 162.4 in 4125 mm |
Width – Minimum | 75 in 1906 mm |
Width – Maximum | 78.3 in 1989 mm |
Height – Maximum | 75 in 1906 mm |
Dry Weight – Genset (minimum) | 12039 lb 5461 kg |
Dry Weight – Genset (maximum) | 13030 lb 5910 kg |
Standard Equipment
Air Inlet System
- Air cleaner, single element canister type with service indicator
Control Panel
- GCCP Control panel
- DC volts
- Environmental sealed front face
- kVA (per phase, average & percent)
- Voltage adjust
- Compatible with the following optional modules:
- Low coolant level
- RPM
- Engine cycle crank
- Over/under frequency (81 o/u)
- Programmable protective relaying functions:
- kVAr (per phase, average & percent)
- coolant temperature
- Local annunciator
- Reverse reactive power (kVAr) (32RV)
- 2 Programmable digital outputs
- Emergency stop
- Amps (per phase & average)
- Volts (L-L & L-N)
- Failure to start (overcrank)
- Speed adjust
- 24 Volt DC operation
- Remote Serial annunciator
- kW (per phase, average & percent)
- Low coolant temperature
- High coolant temperature
- Over/under voltage (27 / 59)
- Reverse power (kW) (32)
- Run/auto/ stop/control
- Operating hours
- Customer data link (Modbus RTU)
- Power factor (per phase & average)
- Generator temperature monitoring module
- 6 programmable digital inputs
- Overspeed
- Text alarm/event descriptions
- 4 programmable relay outputs (Form A)
- kW-hr (total)
- Features include:
- Remote CAN annunciator
- Digital I/O module
- Generator phase sequence
- Low oil pressure
- Warning/shutdown with common LED indication of shutdowns for:
- Accessory module data link
- Emergency stop pushbutton
- Serial annunciator module data link
- Frequency (Hz)
- 2 Programmable relay outputs (Form C)
- Oil pressure (psi, kPa or bar)
- Digital indication for:
- Communications
- Overcurrent (50 / 51)
Cooling System
- Caterpillar extended life coolant
- Coolant level shutdown
- Radiator with guard (Sized for 50 degrees C)
- Fan and belt guards
- Coolant drain line with valve, piped to edge of base
Exhaust System
- Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose
Fuel System
- Water seperator
- Flexible fuel lines terminated on base
- Primary and Secondary fuel filters
- Fuel priming pump
Generator and Attachments
- Class H insulation
- 2:1 Volts/Hz
- 3-phase sensing
- Class F temperature rise
- 12 Leads
- VR6 voltage regulator
- Busbar termination
- Reactive droop
- SR4B self excited
Governing System
- Cat electronic governor
Lube System
- Lubricating oil
- Oil drain line with valve, piped to edge of base
- Fumes disposal, piped to front of radiator
- Oil filter
Mounting System
- Base, formed steel with linear vibration isolators between base and engine-generator
Starting / Charging System
- 45 amp Charging alternator
- Fuel shutoff solenoid
- Battery with rack, cables
- 24 volt starting motor
Optional Equipment
Air Inlet System
- Heavy duty air cleaners
- Open element air cleaners
- Dual element air cleaners
Circuit breakers
- 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip
- 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
Control Panel
- GCCP Control panel
- Vandal proof panel door
- Remote custom annunicator
- Ground fault relay
- Common alarm/shutdown relay
- Generator running VFC
- GCCP Control panel
- Local discrete I/O package
- First local annunicators
- Generator temperature monitoring package
Cooling System
- Jacket water heaters
- Radiator duct flange
European Certifications
- Eurasian Conformity (EAC) mark
Exhaust System
- Through wall installation kit
- Manifold and turbocharger guards
- Elbow kit
- Mufflers
Generator and Attachments
- Digital voltage regulator
- Oversize and premium generators
- Permanent magnet excitation (PMG)
- Space heater
Lube System
- Manual sump pump
Mounting System
- Fuel tank base (1200 ltr)
Special Tests / Reports
- PGS Test report @ 0.8 power factor
- PGS Test report @ 1.0 power factor
Starting / Charging
- Battery disconnect switch
- Oversize batteries
- Battery chargers
- Heavy duty starting system
Governing System
- Electronic load share