Main content

Cat

3412C | 900 kVA 50Hz Generator Set

Maximum Rating

680 kVA

680 kVA

Minimum Rating

680 kVA

680 kVA

Emissions/Fuel Strategy

Low Fuel Consumption

Low Fuel Consumption

Overview

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Media

Photos

360° View

Exterior

360° Exterior view. Double click on the image to zoom in on any area of the product.

Features

Details

Specifications

Spec Value
Maximum Rating 680 kVA 680 kVA
Minimum Rating 680 kVA 680 kVA
Emissions/Fuel Strategy Low Fuel Consumption Low Fuel Consumption
Voltage 380 to 415 Volts 380 to 415 Volts
Frequency 50 Hz 50 Hz
Speed 1500 rpm 1500 rpm
Duty Cycle Standby, Prime Standby, Prime
Spec Value
Engine Model 3412C TA, V-12, 4-Stroke Water-Cooled Diesel 3412C TA, V-12, 4-Stroke Water-Cooled Diesel
Bore 5.4 in 137.2 mm
Stroke 6 in 152.4 mm
Displacement 1648.86 in³ 27.02 l
Compression Ratio 13:01 13:01
Aspiration Turbocharged, Air to Air Aftercooled Turbocharged, Air to Air Aftercooled
Fuel System Pump and Lines Pump and Lines
Governor Type ADEM™ A5 ADEM™ A5
Spec Value
Length – Maximum 162.4 in 4125 mm
Width – Minimum 75 in 1906 mm
Width – Maximum 78.3 in 1989 mm
Height – Maximum 75 in 1906 mm
Dry Weight – Genset (minimum) 12039 lb 5461 kg
Dry Weight – Genset (maximum) 13030 lb 5910 kg

Standard Equipment

Air Inlet System

  • Air cleaner, single element canister type with service indicator

Control Panel

  • GCCP Control panel
  • Emergency stop pushbutton
  • Overspeed
  • Text alarm/event descriptions
  • Low coolant temperature
  • Frequency (Hz)
  • Overcurrent (50 / 51)
  • 4 programmable relay outputs (Form A)
  • Volts (L-L & L-N)
  • Programmable protective relaying functions:
  • Warning/shutdownn with common LED indication of shutdowns for:
  • 24 Volt DC operation
  • Over/under voltage (27 / 59)
  • Engine cycle crank
  • Over/under frequency (81 o/u)
  • Remote CAN annunciator
  • Remote Serial annunciator
  • kW (per phase, average & percent)
  • Digital I/O module
  • Failure to start (overcrank)
  • Low oil pressure
  • Low coolant level
  • Run/auto/ stop/control
  • 6 programmable digital inputs
  • Accessory module data link
  • Features include:
  • Compatible with the following optional modules:
  • Serial annunciator module data link
  • kVA (per phase, average & percent)
  • Voltage adjust
  • RPM
  • Generator temperature monitoring module
  • kVAr (per phase, average & percent)
  • 2 Programmable relay outputs (Form C)
  • DC volts
  • Communications
  • Local annunciator
  • Power factor (per phase & average)
  • Speed adjust
  • Emergency stop
  • Reverse power (kW) (32)
  • coolant temperature
  • Digital indication for:
  • Reverse reactive power (kVAr) (32RV)
  • Customer data link (Modbus RTU)
  • kW-hr (total)
  • Amps (per phase & average)
  • High coolant temperature
  • Generator phase sequence
  • Oil pressure (psi, kPa or bar)
  • Operating hours
  • 2 Programmable digital outputs
  • Environmental sealed front face

Cooling System

  • Fan and belt guards
  • Radiator with guard (Sized for 50 degrees C)
  • Coolant drain line with valve, piped to edge of base
  • Coolant level shutdown
  • Caterpillar extended life coolant

Exhaust System

  • Stainless steel exhaust flex with ANSI style outlet flange, gasket, bolts and mating weld flange, shipped loose

Fuel System

  • Primary and Secondary fuel filters
  • Water seperator
  • Flexible fuel lines terminated on base
  • Fuel priming pump

Generator and Attachments

  • 3-phase sensing
  • Busbar termination
  • SR4B self excited
  • 2:1 Volts/Hz
  • Class F temperature rise
  • 12 Leads
  • Class H insulation
  • Reactive droop
  • VR6 voltage regulator

Governing System

  • Cat electronic governor

Lube System

  • Oil drain line with valve, piped to edge of base
  • Oil filter
  • Fumes disposal, piped to front of radiator
  • Lubricating oil

Mounting System

  • Base, formed steel with linear vibration isolators between base and engine-generator

Starting / Charging System

  • Fuel shutoff solenoid
  • 45 amp Charging alternator
  • Battery with rack, cables
  • 24 volt starting motor

Optional Equipment

Air Inlet System

  • Dual element air cleaners
  • Heavy duty air cleaners
  • Open element air cleaners

Circuit breakers

  • 1250, 1600 Amp, 3 pole, IEC 100% rated, 24 volt DC shunt trip
  • 1600 Amp, 3 pole, Non-UL, 100% rated, 24 volt DC shunt trip

Control Panel

  • Ground fault relay
  • Vandal proof panel door
  • First local annunicators
  • Common alarm/shutdown relay
  • Remote custom annunicator
  • GCCP Control panel
  • Generator running VFC
  • GCCP Control panel
  • Local discrete I/O package
  • Generator temperature monitoring package

Cooling System

  • Radiator duct flange
  • Jacket water heaters

European Certifications

  • Eurasian Conformity (EAC) mark

Exhaust System

  • Manifold and turbocharger guards
  • Through wall installation kit
  • Elbow kit
  • Mufflers

Generator and Attachments

  • Permanent magnet excitation (PMG)
  • Space heater
  • Digital voltage regulator
  • Oversize and premium generators

Lube System

  • Manual sump pump

Mounting System

  • Fuel tank base (1200 ltr)

Special Tests / Reports

  • PGS Test report @ 0.8 power factor
  • PGS Test report @ 1.0 power factor

Starting / Charging

  • Battery disconnect switch
  • Heavy duty starting system
  • Battery chargers
  • Oversize batteries

Governing System

  • Electronic load share

Sign up for Riggs Cat Emails