Frequency

60 Hz

60 Hz

Natural Gas Rating

200 eKW

200 eKW

Emissions/Fuel Strategy

U.S. EPA Certified for Non-Emergency Application

U.S. EPA Certified for Non-Emergency Application

Overview

The Cat® spark-ignited generator product line for stationary applications feature permanent magnet excitation, amortisseur winding, skewed stator, voltage adjustment through the EMCP controller, Class H winding insulation and 2/3 pitch incorporated.

Media

Photos

Features

Details

Specifications

Spec Value
Frequency 60 Hz 60 Hz
Natural Gas Rating 200 eKW 200 eKW
Emissions/Fuel Strategy U.S. EPA Certified for Non-Emergency Application U.S. EPA Certified for Non-Emergency Application
Displacement 864.71 in³ 14.17 l
Fuel Type Natural Gas Natural Gas
Speed 1800 rpm 1800 rpm
Spec Value
Engine Model 14.2 L Spark - Ignited 14.2 L Spark - Ignited
Fuel System Carburetor, Down Draft Carburetor, Down Draft
Aspiration Turbocharged-Aftercooled Turbocharged-Aftercooled
Governor Type Electronic Electronic
Compression Ratio 9.5:1 9.5:1
Bore 5.31 in 134.87 mm
Stroke 6.5 in 165.1 mm
Spec Value
Length 127.95 in 3250 mm
Width 52.93 in 1344.5 mm
Height 67.37 in 1711.2 mm
Weight 5756 lb 2610.9 kg

Standard Equipment

Cooling

  • Factory-installed radiator
  • Closed coolant recovery system
  • 50/50 Ethylene glycol antifreeze
  • Standard ambient temperatures up to 50°C (122°F)
  • Radiator and cooling fan complete with protective guards

Air Inlet

  • Single element air filter

Fuel

  • Fuel pressure test po
  • Primary and secondary fuel shut-off
  • Low fuel pressure switch
  • Dual lock off valves
  • NPT connection
  • Natural Gas or LP Vapor

Exhaust

  • Exhaust outlet with 3” pipe

Generator

  • Full load capacity alternator
  • Permanent magnet excitation
  • Class H insulation material
  • Integrated Voltage Regulator
  • Matched to the performance and output characteristics of Cat engines
  • IP23 Protection

Controls

  • EMCP 4.2 Series generator set controller

Mounting

  • Vibration isolaton (puck type)
  • Rubber vibration isolators

Electric Starting and/or Prelube

  • Engine electrical system
  • Solenoid activated starter motor
  • Battery cables

Electric Power - Package Serial Number Prefix

  • Battery charging alternator

Governor

  • Electronic governor (non adjustable)

Control Panel

  • EMCP 4.2 Series generator set controller

Starting/Charging

  • 12 volt starting motor
  • Batteries with rack and cables

Optional Equipment

Starting/Charging

  • Battery charger – UL Listed 10 amp
  • Charging alternator
  • Jacket water heater
  • Battery heater

General

  • UL 2200 package
  • Enclosures: sound attenuated, weather protective
  • CSA Certification
  • Suitable for Use as Service Equipment (SUSE)
  • Automatic transfer switches (ATS)

Generator

  • Shunt trip and auxiliary contact breaker
  • Thermal magnetic or electronic trip MCCBs
  • Anti-condensation heater
  • Excitation: [ ] Permanent Magnet Excited (PM)
  • Anti-condensation heater
  • Oversize and premium generators