Main content

Caterpillar

Cat C32 ACERT Generator Set (IMO II)

C32 ACERT generator sets incorporate a separate circuit aftercooling system (SCAC) for all configurations. The primary advantage of the SCAC systsem is reduced aftercooler corrosion since no sea water circulates through the aftercooler. Many other improvements on these engines contribute to minimizing owning and operating costs. The IMO II and EU Stage IIIA compliant ratings are available with heat exchanger or keel cooled options. Heat exchanger configurations have an optional front mounted sea water pump.

Media

Photos

360° View

Exterior

360° Exterior view. Double click on the image to zoom in on any area of the product.

Features

Details

Specifications

Spec Value
Minimum Rating 550 eKW (688 kVA) 550 eKW (688 kVA)
Maximum Rating 940 ekW (1175 kVA) 940 ekW (1175 kVA)
Frequency 50 Hz or 60 Hz 50 Hz or 60 Hz
Speed 1500 rpm (50 hz) or 1800 rpm (60 hz) 1500 rpm (50 hz) or 1800 rpm (60 hz)
Emissions/Fuel Strategy IMO II IMO II
Spec Value
Aspiration Twin Turbocharged-Aftercooled Twin Turbocharged-Aftercooled
Bore 5.7 in 145 mm
Stroke 6.4 in 162 mm
Displacement 1959 in³ 32.1 l
Governor Type Electronic Electronic
Fuel System Diesel Diesel
Engine Model Vee 12, 4-Stroke-Cycle Diesel Vee 12, 4-Stroke-Cycle Diesel
Spec Value
Length 168.34 in 4275.9 mm
Width 65.79 in 1671.1 mm
Height 70.86 in 1800 mm
Weight – Estimated 15721 lb 7131 kg
Spec Value
Excitation permanent magnet (PMG) permanent magnet (PMG)
Pitch 2/3 2/3
Number of Poles 4 4
Number of Bearings 2 roller bearings 2 roller bearings
Number of Leads 6 6
Insulation Class H Class H
Voltage Regulation ± 0.5% (steady state) ± 0.5% (steady state)
Frame Size 1423, 1467 1423, 1467
IP Rating Drip Proof IP 23* Drip Proof IP 23*
Alignment Closed-coupled adapter Closed-coupled adapter
Wave Form Deviation – Line to Line < 3.0% < 3.0%
Voltage Regulator Cat® Digital Voltage Regulator (CDVR) Cat® Digital Voltage Regulator (CDVR)
Telephone Influence Factor (TIF) < 50 < 50

Standard Equipment

AIR INLET SYSTEM

  • Separate circuit after-cooled (SCAC)
  • Turbocharger, jacket water cooled
  • Turbocharger inlet, 152 mm (6 in) OD straight connection

CONTROL SYSTEM

  • If an EMCP panel or MGCP option is not chosen as optional equipment, then start/stop controls must be provided by the customer
  • Electronic diagnostics and fault logging
  • Engine Protection Mode for extended ambient conditions
  • Electronic fuel/air ratio control

COOLING SYSTEM

  • Separate Circuit After-Cooling (SCAC) for Heat Exchanged (HEX) & Keel cooled engines
  • Jacket Water (JW) and SCAC Heat Exchangers Shell & Tube for HEX cooled engines
  • SCAC pump, gear driven
  • Jacket water pump, gear driven
  • Sea water pump, bronze impeller, gear driven, for HEX cooled engines only
  • Jacket water HEX with Sea water pump Connections: 76.2 mm (3in) ID Standard
  • 4 Bolt ANSI Flange Connection
  • Jacket water HEX without Sea water pump Connection: 2.5″ hose barb connection (inlet), 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange (outlet)
  • Keel Connections: 76.2 mm (3in) ID Standard 4 Bolt ANSI Flange Connection
  • SCAC and JW shunt tanks for maintaining proper Pump inlet pressures

EXHAUST SYSTEM

  • Water-cooled exhaust manifold & turbocharger
  • 4 Bolt 130 mm (5.12 in) diameter flanged outlet

FLYWHEELS & FLYWHEEL HOUSINGS

  • Flywheel Housing, SAE No. 0
  • Flywheel, 18 inch, 136 teeth
  • SAE standard rotation

FUEL SYSTEM

  • Duplex Fuel Filters, Spin-on, RH service
  • Fuel connections size: Supply JIC Deg -10 (7/8 – 14), Return JIC 37 Deg -8 (3/4 -16)
  • Plate-type fuel cooler installed behind Aftercooler Shunt Tank
  • Fuel transfer pump, gear driven
  • Manual fuel priming pump

GENERATORS AND GENERATOR ATTACHMENTS

  • SR5 form wound
  • 2 roller bearings
  • Permanent magnet excitation
  • 4 pole, 6 leads, Series Star connected
  • Caterpillar’s Digital Voltage Regulator (CDVR)
  • Marine Class H insulation, Class F temperature rise
  • Surface mounted platinum (PT100) 3-wire RTDs, 2 per phase on stator and one each on support bearings
  • Anti-condensation space heaters (2 elements – 240 VAC, 1000 Watts
  • IP23 Protection suitable for use with Fixed Water Based Local Application Fire Fighting Systems (FWBLAFFS)
  • System IV insulation for harsh environment protection

LUBE SYSTEM

  • Simplex oil filters, RH service
  • Deep sump oil pan
  • RH service oil filler locations
  • RH service dipstick
  • Oil pump, gear driven

MOUNTING SYSTEM

  • Formed C-channel rails, 300mm (11.81in) height
  • Six shipped loose combined helical spring/rubber isolators for installation below package base

GENERAL

  • Front damper guard
  • Common electrical bonding point on HEX and KEEL cooled engines

Optional Equipment

Alarm and Protection

  • Remote Panels
  • MCS Controller
  • Power analyzer module
  • oil level, exhaust temperature, air starting pressure, heat exchanger pressure sensors

EXHAUST SYSTEM

  • Dry Elbows
  • Flexible Fitting
  • Flange
  • Muffler
  • Muffler Spark Arresting
  • Rain Cap

AIR INLET SYSTEM

  • Air Inlet Cleaner
  • Closed Crankcase Ventilation
  • Air inlet adapter

CHARGING SYSTEM

  • Battery Chargers, Charging Alternators

CONTROL SYSTEM

  • Load Sharing Attachment

FUEL SYSTEM

  • Water Separator

LUBE SYSTEM

  • Duplex Oil Filters, Sump Pump

PROTECTION SYSTEM

  • Fuel and Oil Shielding

STARTING SYSTEM

  • Electric Starting Motors – Single 24 Volt
  • Air Starting Motor
  • Dual Starting Motors (Electric and Air)
  • Air Start Accessories
  • Starting Aids – JW Heaters
  • Battery Sets – 24 Volt – Dry